REE-5001/REE-5501 2 Installation Guide













 



   









© 2012 KMC Controls, Inc. 809-019-03G
KMCControls,Inc.
19476 Industrial Drive
New Paris, IN 46553
574.831.5250
www.kmccontrols.com; [email protected]
Important Notices
The material in this document is for information pur-
poses only. Thecontentsandtheproductitdescribes
aresubjecttochangewithoutnotice. KMC Controls,
Inc. makes no representations or warranties with
respect to this document. In no event shall KMC Con-
trols, Inc. be liable for any damages, direct or incidental,
arising out of or related to the use of this document.




























NOTE: Minimums must be sucient for reheat.
Sample Application
NOTE: For more
information about
this CSP-5001 and
CTE-5103 example,
see the CSP-
5001/5002 VAV
Flow Controller-
Actuators
Application Guide.
NOTE: Triacoutputsare
for24VACloads
only.
NOTE: FortheREE-5001,
thephasesideof
thetransformer
connectsto
the“common”
sideoftheload
(contactors).
Maintenance
No routine maintenance is required, however protec-
tion from extremes of humidity and dirt is recom-
mended. Careful installation will also ensure long
term reliability and performance.
Stage Status
Normal Triac Voltage (Approximate, and With Load)
Across Load
(Terminal ~/Phase to
Terminal 1, 2, or 3)
Across Triac
(Terminal –/Neutral to
Terminal 1, 2, or 3)
On 24 VAC 1 VAC
Off 0 VAC 24 VAC
Troubleshooting
Check the wiring.
Check the voltage from the thermostat/controller
(measured from Terminal T to Terminal
–/Neutral). (See the voltage charts aboveandon
thepreviouspage.)
Check the voltage across the triac and load. (See
the chart below.)