SSS-1000 Series 2 Installation Guide
© 2014 KMC Controls, Inc. 655-019-01L
KMC Controls, Inc.
19476IndustrialDrive
NewParis,IN46553
574.831.5250
www.kmccontrols.com
Select Specifications
Material Lightgray(SSS-100x)oral-
mond(SSS-101x)ABS/polycar-
bonate(UL94-5V)
Connection 1/4"nipple(SSS-100x)for3/8"
ODpolyethylenetubingor
3/16" nipple (SSS-101x) for
1/4" OD tubing
K Factors See the data sheet for addi-
tional information!
Maintenance
Sensing orices must be kept free of dust ac-
cumulation or debris. Thesensorsaredesignedfor
dependable,long-termreliabilityandperformance.
Important Notices
TheKMClogoandKMCControlsareregistered
trademarksofKMCControls,Inc.
Allrightsreserved.Nopartofthispublicationmay
bereproduced,transmied,transcribed,storedina
retrievalsystem,ortranslatedintoanylanguagein
anyformbyanymeanswithoutthewrienpermis-
sionofKMCControls,Inc.
Thematerialinthisdocumentisforinformation
purposesonly.The contents and the product it
describes are subject to change without notice.
KMCControls,Inc.makesnorepresentationsor
warrantieswithrespecttothisdocument.Innoevent
shallKMCControls,Inc.beliableforanydamages,
directorincidental,arisingoutoforrelatedtothe
useofthisdocument.
More Information
For additional K factor
andotherinformation,
see the SSS-1000 Series
Data SheetontheKMC
website(www.kmccon-
trols.com).
“Cubic Feet Per Minute (CFM)” K Factors
Round
Duct Size
(Diameter)
K
CFM
Factor
SSS-10x2 SSS-10x3 SSS-10x4 SSS-10x5
4 301 NA NA NA
5 470 NA NA NA
6 677 648 NA NA
7 922 882 NA NA
8 1204 1152 1117 NA
9 1524 1458 1414 NA
10 1882 1800 1745 1745
12 2710 2592 2513 2513
14 3688 3528 3421 3421
16 4817 4608 4468 4468
18 6097 5832 5655 5655
22 9107 8711 8447 8447
24 10838 10367 10053 10053
“Feet Per Minute” K Factors
Sensor Model K
FPM
SSS-10x2 3450
SSS-10x3 3300
SSS-10x4 3200
SSS-10x5 3200
NOTE: For the appropriate sensor “K” factor:
• For digital VAV controllers needing K
CFM
for setup,
see the “CFM” chart below and the data sheet for
additional information. For rectangular ducts,
K
CFM
= K
FPM
x (W" x H"/144)
2
(with duct cross-
section measurements in inches).
• For CSC-2000 series, CSC-3000 series, and CSP-
4000 series controllers (needing K
FPM
for setup),
see the “Feet Per Minute” chart below and the
data sheet for additional information.
• For CSP-5000, KMD-7000, and BAC-7000 series
that operate differently—see their respective in-
stallation guides and application guides for more
information.