THE-1002 1 Installation Guide
Installation Guide
Duct-Mounted Humidity Transmitter w/ Temperature Sensor
THE-1002
Mounting
Mounting 1
Wiring 2
More Information 2
Maintenance 2
Important Notices 2
NOTE: Thesensorshouldbeinstalledinastraight
sectionofductawayfromheating,cooling,
orhumidierelements.
1. Intheduct,drilla1-1/8"clearancehole(forthe
sensorprobe).
2. Measure1-5/8"toeithersideofthecenterofthe
clearanceholeanddrilltwoholesformounting
screws.
3. FromtheTHE-1002,removethetwocover
screws,cover,andthedesiredknock-outforthe
conduit.
4.
InserttheTHE-1002probeintotheduct.
5. Insertthetwomountingscrewsandtighten
them.
6.
FastenconduittotheTHE-1002.
7. Throughtheconduit,feedwirestothecontroller
andmaketheappropriateconnections.(Seethe
Wiringsectiononthenextpage.)
8. Aerwiring,plugtheconduitwithplumber’s
puy,painter’spuy,caulk,orothersealantto
preventairinltration.
9. Reinstallthecoverandcoverscrews.Besure
thescrewsgothroughthemountingholesof
therelaymodule,securingthebackoftherelay
moduletothebacksideofthecover.