Kmc-controls FlexStat Operation Guide User Manual Page 17

  • Download
  • Add to my manuals
  • Print
  • Page
    / 46
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 16
FlexStat 17 Operation Guide, Rev. R
(Advanced) BACnet Device Properties
DEVICE
INSTANCE:
NAME: FlexStat_101
LOCATION: KMC Controls
1
To set the BACnet device instance, name, and
location, press:
1. Up/Down to move among entries.
2. Enter to select.
NOTE: InrmwareversionsR1.3.0.4andearlier,
theFlexStatcouldalsoberestartedor
restored to factorydefaultsfromthis
menu. In R2.0.x, this function was moved to
a separate menu. See (Advanced) Restart/
Restore on page 18 and Reseing the FlexStat
on page 26 for more information about that
function.
(Advanced) Inputs
INPUTS
1: SPACE TEMP
2:
3: MIXED AIR TEMP
4: OUTSIDE AIR TEMP
5: SPACE HUMIDITY
7: REMOTE SPACE TEMP
8: AI_08
DISCH AIR TEMP
INPUT #2
DISCH AIR TEMP
VALUE: 60.0° F
CAL. OFFSET: 0.0
OUT-OF-SERVICE: FALSE
FILTER WEIGHT: 6
SENSOR:
10K TYPE III
Inputs vary according to model, selected application,
and selected application options. See (Advanced) Ap-
plication and Additional Setup on page 7.
Value will show a temperature reading or a voltage
(0.0 to 3.0), depending on the sensor. Analog sensors
(built-in or external) can be calibrated by adjusting
the Calibration Oset value (see the FlexStatAppli-
cationGuide for details).
FilterWeight smooths (dampens) input value read-
ings, reducing sensitivity to noise and temperature
spikes. Smaller lter weight values (more sensitive)
cause the sensor readings to react more quickly to
sudden changes, and larger values (more stable)
cause sensor readings to react more slowly to sudden
changes. Areas subject to sudden swings of tempera-
ture from factors such as door openings and closings
may benet from adjusting the lter weight. Tempo-
rarily reducing lter weight may also be helpful for
some diagnostic or commissioning purposes (but the
defaults should be restored for normal operation).
For much more information, see the FlexStatAppli-
cationGuide.
CalibrationOset can be used to calibrate an analog
input by changing the value. For details of calibrat-
ing the internal temperature sensor, see the FlexStat
ApplicationGuide. (A CO
2
sensor has a dierent
calibration method, using a gas cylinder—see the
FlexStatApplicationGuide.)
Out-of-Service: False” means the input is active (not
out of service). If it is “true,” the input is inactive.
The FlexStat menu only shows the status. The status
can only be changed through BACstage or TotalCon-
trol.
(Advanced) Temp. Setpoint Limits
LIMITS
OCC MIN CLG:
OCC MAX HTG: 80° F
UNOCC MIN CLG: 66° F
UNOCC MAX HTG: 80° F
MIN SETPT DIFF: 2° F
66° F
This menu permits changes to the minimum and
maximum allowed user/operator setpoint values.
NOTE: For Minimum Setpoint Dierential, see the
diagram.


































Page view 16